• Skip to primary navigation
  • Skip to main content
  • Skip to primary sidebar
  • Skip to footer
  • Skip to footer navigation
Motor and Generator Institute

Motor and Generator Institute

Emergency and Standby Power Education

  • Home
  • About
  • Blog
  • Certification
  • Contact
  • My Account

Testing EPSS Circuit Breakers

Published: September 30, 2019 Dan Chisholm Sr

Question 1: To meet the requirements of NFPA 110, 8.4.7 do I even need to complete a test proving that each transfer switch will start the EPS (generator) and transfer the load to each Life Safety (LS) and Critical Branch (CB) automatic transfer switch (ATS) within 10 seconds, or is the monthly test sufficient?

Answer 1: NFPA 110, 8.4.7, only references breakers in the emergency distribution between the EPS (generator) and the ATSs (transfer switches); not the normal (utility) distribution breakers. Therefore, these breakers are not used for the monthly test…only opening normal feed breakers are used as an option to utilizing the test switch on a selected LS or CB ATS.

Note 1: All ATSs must be transferred during the monthly test.

Note 2: However, NFPA 99 nor 110 require each LS and CB ATS to be tested monthly to prove the transfer time of 10 seconds or less

Reference: NFPA 110, 8.4.7: EPSS circuit breakers for Level 1 system usage, including main and feed breakers between the EPS [generator] and the transfer switch load terminals, shall be exercised annually with the EPS in the “off” position. [emphasis added]

Question 2: If I do need to complete separate tests, can I electronically transfer load with the test switch on each transfer switch, or do I need to open the breaker to simulate a power outage?

Answer 2: Not applicable when referencing 8.4.7. However, you are allowed to use a test switch for transferring power at each ATS, including the ATS being used to start the test.

Question 3: Is 8.4.7 referencing the breaker at the EPS and the transfer switches?

Answer 3: Yes, and yes, but only the emergency power feed breaker to an ATS, not the normal power feed breaker.

Summary: NFPA 110, 8.4.7 does not apply to monthly testing/transfer of ATSs. It is a test to confirm the emergency breaker(s) itself will function. Typically, the EPS breaker is located on the EPS. The feed breakers from the generator to each ATS are usually located in a separate room dedicated to the EPSS distribution center.

If you have a parallel set up, then the breakers in the parallel cabinet exercise themselves automatically every month.

About Dan Chisholm Sr

Motor and Generator Institute (MGI) was formed in 1995 by Dan Chisholm, Sr, CHEPP. Dan is currently President of MGI Consulting Services and serves as the Chairman of the National Fire Protection Association’s Technical Committees responsible for NFPA 110, Emergency and Standby Power Systems, NFPA 111, Stored Electrical Energy Emergency and Standby Power Systems, and a technical committee member of the Electrical Section of NFPA 99, Health Care Facilities Code, while also serving as a primary emergency power consultant to the U.S. Army Medical Department (AMEDD) and the Department of Defense. Click here to learn more about Dan.

Primary Sidebar

Educational Programs

  • Sample Certificate CHEPP® Certification $299

Recent Posts

  • Lessons Learned from the Bombing in Nashville
  • How to obtain proper exhaust gas temperatures
  • CHEPP Educational Video Game
  • CMS Requirements for Emergency Power and Temperature Control
  • Emergency Power Off (EPO) Testing

Footer

About Us

Motor and Generator Institute offers online training for personnel involved in the operation, maintenance, testing, and compliance of an emergency power supply system (EPSS).

Learn More

Contact Us

Address: PO Box 560042, Orlando, FL 32856
Phone: +1 407-839-1270
Email: danny.chisholm@mgisys.com
  • LinkedIn
  • Twitter

Copyright © 2021 · MGI Systems, Inc.

  • Certification
  • Course
  • Manual
  • Pricing
  • Teams